INSTALLER SETTING
Menu hierarchy & Setting Explanation
Detailed
explanation
Available Setting options
(range)
Unit Default
AUTO MODE
Seasonal
auto temp
Mode
Definition if weather-dependency (Auto mode) is
applied to heating and cooling or heating only.
O
Heating only /
Heating & Cooling
- Heating only
Outdoor
temperatures
O1
Graphic setting of outdoor temperature ranges for
heating and cooling in Auto mode.
-25 ~ 35 °C -10
O2 -25 ~ 35 °C 18
O3 10 ~ 46 °C 30
O4 10 ~ 46 °C 40
Target
temperatures
Circuit 1
A1
Graphic setting of target temperatures in
Heating/Cooling operation for Circuit 1 & 2.
- If setting 'Configuration/Control method =
Air', then targets for Room air are defined here.
- If setting 'Configuration/Control method =
Water or Water+Air', then targets for outlet or
inlet temperature are expressed.
16 ~ 30 °C 21
A2 16 ~ 30 °C 19
A3 18 ~ 30 °C 21
A4 18 ~ 30 °C 19
W1 15 ~ 75 °C 50
W2 15 ~ 75 °C 40
W3 5 ~ 27 °C 12
W4 5 ~ 27 °C 10
Circuit 2
A1 16 ~ 30 °C 21
A2 16 ~ 30 °C 19
A3 18 ~ 30 °C 21
A4 18 ~ 30 °C 19
W1 15 ~ 75 °C 35
W2 15 ~ 75 °C 28
W3 5 ~ 27 °C 18
W4 5 ~ 27 °C 16