162
INSTALLER SETTING
Connectivity - 3rd party boiler
Either the heat pump or the boiler is used for space heating (Bivalent-alternative operation)
Two different modes are available to switch-over between heat pump and boiler:
- Manual: The boiler is activated and de-activated by User setting ‘Function/3rd party boiler’.
- Auto: The boiler output is activated based on outdoor temperature.
The bivalent temperature (Default: -7 °C) and the switch-over hysteresis (Default: 4 K) can be
adjusted by setting.
1) Seasonal auto temp/Outdoor temp/O1
2) Connectivity/3rd party boiler/Temp
3) Connectivity/3rd party boiler/Hysteresis
4) Seasonal auto temp/Outdoor temp/O2
NOTE
Prices for electricity and fuel, as well as the maximum capacity of the heat pump must be
considered when changing the Bivalent temp.
Outside
temp.
Capacity
Only boiler operation
Only heat pump operation
T
Design
1)
Bivalent
2)
T
Off
4)
T
<= Heat pump
capacity
<= Boiler
capacity
Hysteresis
3)