INSTALLER SETTING
ENGLISH
NOTE
To use this function DIP switch No.1 of SW1 must be set to ON and No.2 to Off.
Connectivity - Modbus address(HEX)
This function allows control of the heat pump by external devices.
Modbus memory map
- Baud Rate : 9 600 bps
- Stop Bit : 1 stop bit
- Parity : None Parity
Register Description Value explanation
00001 Enable/Disable (Heating/Cooling) 0 : Operation OFF / 1 : Operation ON
00002 Enable/Disable (DHW) 0 : Operation OFF / 1 : Operation ON
00003 Silent Mode Set 0 : Silent mode OFF / 1 : Silent mode ON
00004 Trigger Disinfection operation 0 : Keep status / 1 : Operation start
00005 Emergency Stop 0 : Normal operation / 1 : Emergency stop
00006 Trigger Emergency Operation 0 : Keep status / 1 : Operation Start
Coil Register (0x01)