158
INSTALLER SETTING
Discrete Register (0x02)
Register Description Value explanation
10001 Water flow status 0 : Flow rate ok / 1 : Flow rate too low
10002 Water Pump status 0 : Water Pump OFF / 1 : Water Pump ON
10003 Ext. Water Pump status 0 : Water Pump OFF / 1 : Water Pump ON
10004 Compressor status 0 : Compressor OFF / 1 : Compressor ON
10005 Defrosting status 0 : Defrost OFF / 1 : Defrost ON
10006
DHW heating status
(DHW Thermal On/Off)
0 : DHW inactive / 1 : DHW active
10007 DHW Tank disinfection status 0 : Disinfection inactive / 1 : Disinfection active
10008 Silent mode status 0 : Silent mode inactive / 1 : Silent mode active
10009 Cooling status 0 : No cooling / 1 : Cooling operation
10010 Solar pump status 0 : Solar pump OFF / 1: Solar pump ON
10011 Backup heater (Step 1) status 0 : OFF / 1 : ON
10012 Backup heater (Step 2) status 0 : OFF / 1 : ON
10013 DHW boost heater status 0 : OFF / 1 : ON
10014 Error status 0 : no error / 1 : error state
10015
Emergency Operation Available
(Space heating/cooling)
0 : Unavailable / 1 : Available
10016
Emergency Operation Available
(DHW)
0 : Unavailable / 1 : Available
10017 Mix pump status 0 : Mix pump OFF / 1 : Mix pump ON

Table of Contents