INSTALLER SETTING
ENGLISH
Input Register (0x03)
Register Description Value explanation
30001 Error Code Error Code
30002 ODU operation Cycle 0 : Standby(OFF) / 1 : Cooling / 2 : Heating
30003 Water inlet temp. [0.1 °C ×10]
30004 Water outlet temp. [0.1 °C ×10]
30005 Backup heater outlet temp. [0.1 °C ×10]
30006 DHW tank water temp. [0.1 °C ×10]
30007 Solar collector temp. [0.1 °C ×10]
30008 Room air temp. (Circuit 1) [0.1 °C ×10]
30009 Current Flow rate [0.1 LPM ×10]
30010 Flow temp. (Circuit 2) [0.1 °C ×10]
30011 Room air temp. (Circuit 2) [0.1 °C ×10]
30012 Energy State input 0 : Energy state 0; 1: Energy state 1….
30013 Outdoor Air temp. [0.1 °C ×10]
30014 Water pressure [0.1 bar ×10]
39998 Produc Group 0x8X (0x80, 0x83, 0x88, 0x89)
39999 Product Info.
Split : 0 / Monobloc : 3 / High Temp. : 4 /
Medium Temp. : 5 / System Boiler : 6