124
INSTALLER SETTING
Menu hierarchy & Setting Explanation
Detailed
explanation
Available Setting options
(range)
Unit Default
DOMESTIC
HOT WATER
DHW heating duration
Active time Duration how long DHW heating continues
O
5 ~ 95 min 30
Stop time
Duration how long DHW heating is interrupted (if
DHW target is not reached in one cycle)
0 ~ 600 min 30
DHW electric re-heating
DHW heater
usage
- Use: DHW will be re-heated electrically if the heat
pump cycle does not reach the target temp.
within time setting.
- Use disinfection: Electric re-heating is only used
for anti-legionella operation and
in case of emergency.
If 'Use disinfection' is chosen,
the DHW temp. setting range is
limited!
O
Use always / Use
disinfection
- Use always
DHW heater
delay time
After time has elapsed, the DHW boost heater is
released.
10 / 20 / 30 / 40 / 50 / 60 /
90 / 120 / 1440
min 30
DHW re-circulation
Enable re-
circulation
Definition if DHW recirculation pump is connected
or not. If it is used, a Schedule in the main menu
becomes available to set the time frames for
operating the pump.
O
Use / Not use - Not use
On
Definition of recirculation pump cycling pattern
during release schedule. By default, the pump
operates every twenty minutes for 10 minutes
(only during the set Schedule!)
5 ~ 60 min 10
Off 5 ~ 60 min 20
SOLAR
THERMAL
SYSTEM
Solar collector operating
range
Min.
Solar cycle will not start before collector has
reached this temp.
O
5 ~ 50 °C 10
Max.
Solar cycle will not start if collector exceeds this
temp.
60 ~ 200 °C 135
Solar tank temp. Limit Max.
Solar cycle will not start, if DHW tank has reached
its maximum temp.
20 ~ 90 °C 80