INSTALLER SETTING
ENGLISH
Menu hierarchy & Setting Explanation
Detailed
explanation
Available Setting
options (range)
Unit Default
CONNECTIVITY
Energy
state
Energy
state
definition
Energy state 8 Setting whether Energy state 8 is used or not.
O
Not use / Use
Energy state 8 - Heat temp.
Definition how much Heating target temp.
shall increase when Energy State 8 is applied.
0 ~ 30 K -5
Energy state 8 - Cool temp.
Definition how much Cooling target temp.
shall decrease when Energy State 8 is applied.
0 ~ -30 K 5
Energy state 8 - DHW
temp.
Definition how much DHW target temp. shall
increase when Energy State 8 is applied.
0 ~ 50 K 0
Digital
inputs
assignment
State 3 (0:1)
Definition of Energy state 3:
- 3 : Cooling/no effect, Heating/Target +2K,
DHW/Target +5K
- 4 : Cooling/no effect, Heating/no effect,
DHW/Target=80°C
- 5~8 : According setting
"Energy state definition"
O
3 ~ 8 - 3
State 4 (1:1)
Definition of Energy state 4:
- 3 : Cooling/no effect, Heating/Target +2K,
DHW/Target +5K
- 4 : Cooling/no effect, Heating/no effect,
DHW/Target = 80 °C
- 5~8 : According setting
"Energy state definition"
3 ~ 8 - 4
Thermostat control type Setting what type of thermostat is connected
- Heat & Cool
- Heat & Cool/DHW
- DHW only
- Heat & Cool