EasyManua.ls Logo

Liebert Mini-Mate2 MMD24E - Figure 16 Evaporator and Chilled Water Unit Electrical Connections

Liebert Mini-Mate2 MMD24E
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Site Preparation and Installation
29 Liebert
®
Mini-Mate2
Figure 16 Evaporator and chilled water unit electrical connections
Remote Control Panel Connection to TB3-1,2,3,4 connected with field-supplied
thermostat wire (22ga., shielded/ jacketed: available from Emerson or others).
Unit Control Board terminals marked GND, +5V, T-, T+ must be connected to
corresponding terminals on Remote Control Wall Box.
Common alarm connection. Field-supplied 24V
Class 2 wiring to common alarm conn TB1-6 and TB1-7
Entrance for customer
low-voltage connections.
Remote Humidifier Contact
Field-Supplied 24V class 2
wiring to terminals 11 & 12,
located in field wire
compartment
Site monitoring connection. Terminals
TB4-1(+) TB4-2(-) are for connection
of a 2 wire. twisted pair, communication
cable (available from Emerson or others)
to optional Liebert SiteScan
Customer remote alarm connection
field-supplied 24V. Class 2 wiring
to conn TB1-1, TB1-2 & TB1-3
Remote unit shutdown. Replace existing
jumper between Terminals TB1-4 & TB1-5
with normally closed switch having a
minimum 75VA rating. Use field-supplied
24V Class 1 wire.
Optional condensate
pump aux float switch
connection to term
TB1-8 & TB1-9
Field-supplied unit disconnect
switch when factory unit disconnect
switch is not supplied
Factory-installed
disconnect switch
Electric service not by Emerson
Entrance for Customer
High-Voltage Connections
Entrance for Customer
Low-Voltage Connections
Drycooler/Circulating pump
control circuit TB70-71.
Optional w/Econ-O-Cycle
models. Use field-supplied
24V Class 2 wire.
Field-supplied,
field-wired thermostat
wire to remote
wall box
Field-supplied 24V (NEC Class 2 wiring) to
condensing module. (if applicable)
NOTES:
1.Refer to specification sheet for full load amp and wire size amp ratings.
2.Control voltage wiring must be a minimum of 16ga. (1.3mm) for up to
75' (23m) or not to exceed 1 volt drop in control line
DPN000195
Rev. 2
Electrical entrance for
optional condensate
pump
High-Voltage Power Connections. Electric
service connection terminals
Earth ground connection
Connection terminal for field-
supplied earth grounding wire
Heat rejection connection. Field-supplied
24V NEC class 2 wiring. See note 2.
For remote air cooled units from
terminals TB2-1, 2, 3 & 4 in the
Fan/Coil module to wires 1, 2, 3 & 4
in the condensing module
1. 24V GND
2. 24V Supply
3. High Pressure Alarm (OPT)
4. Hot Gas Bypass Connection

Table of Contents

Related product manuals