Alarms
Liebert
®
Mini-Mate2
58
8.1.8 Short Cycle
A Short Cycle Alarm will occur if the compressor system has exceeded 10 cooling start attempts in a
one-hour period. This can be caused by low refrigerant level or room cooling load is small compared to
capacity of the unit. Check for leaks, crimped lines and defective components. If room load is low,
increase sensitivity to reduce cycle.
8.2 Optional/Custom Alarms
8.2.1 Change Filter
Periodically, the return air filters in the evaporator must be changed. The Change Filter alarm
notifies the user that filter replacement is necessary. A differential air pressure switch closes when
the pressure drop across the filters becomes excessive. The switch is adjustable using the procedure
on the switch label.
8.2.2 High Temperature Sensor
The optional high temperature sensor feature is a bimetal operated sensing device with a closed
switch under normal conditions. Connected between pins 1-8 and 1-9, this device will shut down the
entire unit.
8.2.3 Smoke Detected
The smoke detector senses the return air, shuts down the unit upon detection and sends visual and
audible alarm. This smoke detector is not intended to function as or replace any room smoke detection
system that may be required by local or national codes. Locate source of smoke and follow appropriate
emergency procedures.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Mini-Mate2 MMD24E and is the answer not in the manual?

Liebert Mini-Mate2 MMD24E Specifications

General IconGeneral
BrandLiebert
ModelMini-Mate2 MMD24E
CategoryAir Conditioner
LanguageEnglish

Related product manuals