Chapter 3. General Specification
3-9
3.2.4 Rnet LED signal name and indication content
Device
type
LED
Name
Meaning of LED indication LED On LED Off
RUN Indicates the status of CPU module and interface Normal Abnormal
LAS Indicates that communication module is performing LAS
function.
In proceeding
TOKEN Indicates whether communication module has token or not. Has Does not have
TX/RX Indicates whether communication module is transmitting/
receiving or not.
Flicker during communication
LINK-I/F Indicates whether there is TX/RX data. Communicatio
n
Communication OFF
G3L-RUEA
G4L-RUEA
G6L-RUEA
G7L-RUEA
FAULT Indicates the status of communication module. Abnormal Normal
RUN Indicates the status of communication module. Normal Abnormal
TOKEN Indicates whether communication module has token or not. Has Does not have
TX/RX Indicates whether communication module is transmitting/
receiving or not.
In proceeding Flicker
FAULT Indicates whether communication error exists or not. Abnormal Normal
G3L-RREA
G4L-RREA
G6L-RREA
SYS FAULT Indicates whether system error or I/O module error occurred
or not.
Abnormal Normal
For details on LED, see chapter 7.1
3.2.5 Rnet station no. setting
1) Self station no. setting
Applied device
type
Detailed drawing of
station number switch
Contents
G3L-RUEA
G3L-RREA
G4L-RUEA
G4L-RREA
G6L-RUEA
G6L-RREA
G7L-RUEA
0
5
27
×10
0
5
27
×1
(1) Station number can be set from 0 to 63 (Decimal).
(2) Station number setting
(Factory default is 0)
Switch Setting
X 10 Sets ten’s figure of station number
X 1 Sets one’s figure of station number
(3) GM6: The station setting switch is placed in the case.

Table of Contents