Chapter 9. Trouble Shooting
9-9
9.2.7 Error code E03-01: High speed link parameter error
Is the backup battery of
CPU normal?
Parameter error of high speed link
Yes
No
Is the number of
transmission items among
registration items 32 or
more?
Correct the setting of station
number by referring to function
description of high speed link in
6.2.
Are
network type, slot,
and self station number of the
link setting identical with
appropriate
slot?
No
Is setting
method of station number for
each registration item
correct?
Correct the link setting according
to network type, station number,
and slot number of appropriate
slot.
Download parameter again.
Reduce transmission items by
referring to the description of high
speed link function.
No
End
Yes
Yes
Yes
Repair the battery and
download program and
parameter.
No
Are
there duplicated
blocks numbers among registration
items for the same
station.
Correct duplicated blocks for
the same station.
Is Tx/Rx
area relevant among
registration
items?
Set link enable setting to ‘On’.
Yes
No
Adjust the range of Tx/Rx area by
referring to CPU type and base
parameter.
Yes
No

Table of Contents