Chapter 6. Communication Function
6-1
Chapter 6. Communication Function
6.1 Communication Function
6.1.1 General
Communication with Smart I/O module, remote Rnet(GXL-RREA) is executed through High Speed-
Link service.
High Speed Link
Communication is executed by setting the simple parameter through High Speed Link. GMWIN is
used for GLOFA series setting and KELWIN is used for MASTER-K series setting.
1) Setting range of Rnet I/F module
Maximum High Speed Link Contact No. (Rnet Master)
Type Max.
communication
contact no.
Max. sending
contact no.
Max. block
no.
Max. contact no. per
block
G3L-RUEA 3,840 word 1,920 word 2 (0-1) 60 word
G4L-RUEA 3,840 word 1,920 word 2 (0-1) 60 word
G6L-RUEA 3,840 word 1,920 word 2 (0-1) 60 word
Rnet
I/Fmodule
G7L-RUEA 3,840 word 1,920 word 2 (0-1) 60 word
Communication setting when communicating with Slave module
HS Link block setting Address area
TX RX
TRX period
GLOFA-GM TX
HS Link
information
RX
1 1 20ms ~ 10s %QW, %IW P area
Refer to Ch.
6.1.2