10. Advanced functions
10-15
SV-iC5
10.12 Auto restart try
Group LED Display Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
Function
group 2
H26
[Number of Auto Restart
try]
- 0/10 0
H27
[Auto Restart time]
- 0/60 1.0 Sec
This parameter sets the number of times auto restart is activated in H26.
It is used to prevent the system down caused by internal protection function activated by the causes such as
noise.
H26 : Auto restart will become active after the H27. The H26 [Number of Auto restart try] is reduced
by 1 when it is active. If the trip outnumbers the preset restart try, auto restart function is deactivated. If
the setting is reset via the control terminal or the STOP/RST key on the keypad, the number of auto
restart try set by user is automatically entered.
If there is no more trip occurring for 30 sec after Auto restart operation, the H26 is restored to the
preset value.
When operation is stopped due to Low voltage {Lvt} or Emergency stop {EST}, Auto restart will be
deactivated.
After the H27- [Auto Restart time], the motor starts acceleration automatically via speed search
(H22-25).
The following pattern is shown when the H26 – [Number of auto restart try] is set to 2.
Run
Command
Constant
Run
Number of Auto
restart try
2 1 2 1 0 2
Freq
Voltage
Reset
30Sec
Speed Search
operation
Trip occurred
H27

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems SV iC5 Series and is the answer not in the manual?

LS Industrial Systems SV iC5 Series Specifications

General IconGeneral
BrandLS Industrial Systems
ModelSV iC5 Series
CategoryInverter
LanguageEnglish

Related product manuals