10. Advanced functions
10-19
SV-iC5
Parameter Lock
Group LED Display
Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
Function
group 2
H95
[Parameter lock]
-
0/FFF
0
H94
[Password Register]
-
0/FFF
0
This parameter is used to lock the user-set parameters using the password.
See the table below to lock the user-set parameter via the H94 – [Password Register].
Step Description LED Display
1 Go to H95 – [Parameter lock] H95
2 Enter the Prog/Ent () key UL
3
Parameter value can be changed in UL (Unlock) status. While seeing this
message
UL
4 Enter the Prog/Ent () key. 0
5 Enter the password created in H94 (e.g.: 123). 123
6 Enter the Prog/Ent () key L
7 Parameter value cannot be changed in L (Lock) status. L
8 Press either the left (⊳) or right () key. H95
See the table below to unlock the user-set parameter via password.
Step Description LED Display
1 Go to H94 – [Password register] H94
2 Press the Prog/Ent () key L
3 Parameter value cannot be changed in L(Lock) status. L
4 Press the Prog/Ent () key 0
5 Enter the password created in H94 (e.g.: 123). 123
6 Press the Prog/Ent () key UL
7
Parameter value can be changed in UL (Unlock) status. While seeing this
message
UL
8 Press the Prog/Ent () key H95