12. Protective functions
12-8
SV-iC5
I62 [Drive mode select
after loss of
frequency
command]
0
Continuous operation with the
frequency before command loss occurs
1 Free run stop (output cut off)
2 Decel to stop
I54, I55: Multi-function output terminal (MO) or Multi-function relay output (30AC) is used to output
information on loss of frequency command to external sequence.
For example, when I62 is set to 2, I63 to 5.0 sec and I54 to 11, respectively,
Freq
MO
Run
command
Set
freq
5 sec