EasyManua.ls Logo

LS Industrial Systems SV-iE5 Series - Page 50

LS Industrial Systems SV-iE5 Series
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. Function List
7-14
Display Name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
P84
Parity/stop
bit setting
0 ~ 3
Sets communication parity and stop bit.
0 O
Parity bit Stop bit
0 - 1 Stop Bit
1 - 2 Stop Bit
2 Odd Parity 1 Stop Bit
3 Even Parity 1 Stop Bit
P85
Parameter
initialization
0 ~ 3
Initialize the parameters set by a user
to factory defaults
0 X
0
-
1
Initialize both groups
2
Initialize Drive Group
3
Initialize PG Group
P86
Password
registration
0 ~
FFFF
Enter password to prohibit parameter
change. Set it as hexadecimal number
0 O
P87
parameter
change
prohibition
0 ~
FFFF
Prohibit or cancel parameter change
prohibition by using the password set in
P86.
0 O
UL(Unlock)
Enable parameter
change
L(Lock)
Disable parameter
change
P88
Software
version
-
Display inverter software version. Refer
to manual version.
- X
P89
Selecting
communicat
ion protocol
0 ~ 1
0 : Modbus RTU
1 : LSBUS
0 X