Chapter 7. Function List
7-13
Display Name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
P78
Fault
output
select
0 ~ 7
[bit]
Func
.
Set
Operation
when
setting the
number of
auto
restart
try(P38)
Operation
when the
trip other
than low
voltage trip
occurs
Operation
when the low
voltage trip
occurs
2 O
bit 2
bit 1
bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
P79
Inverter
number
1 ~
250
Set for RS-485 communication 1 O
P80 Baud rate 0 ~ 2
Select the Baud rate of the RS-485.
2 O
0
2400 [bps]
1
4800 [bps]
2
9600 [bps]
P81
Drive
mode
select
after loss
of
frequency
command
0 ~ 2
It is used when freq command is gi
ven via
Analog signal(volume/AI) or RS-485.
0 O
0
Continuous operation at the frequency
before its command is lost.
1
Free Run stop (Output cut-off)
2 Decel to stop
P82
Wait time
after loss
of
frequency
command
0.1 ~
120
[sec]
Time inverter determines whether there is the
input frequency command or not. If there is no
frequency command input during this time,
inverter starts operation via the mode selected at
P81.
1.0 O
P83
Communi-
cation
time
setting
2 ~
100
[ms]
When RS-485 communication, waiting time from
TX to the next TX.
5 O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems SV-iE5 Series and is the answer not in the manual?

LS Industrial Systems SV-iE5 Series Specifications

General IconGeneral
BrandLS Industrial Systems
ModelSV-iE5 Series
CategoryInverter
LanguageEnglish

Related product manuals