5-20
LED
display
Address
for
communi
cation
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
I19 A413 [Multi-
function
input
terminal P3
define]
4 Jog operation command 2 O 8-3
5 Multi-Step freq – Low 7-7
I20 A414 [Multi-
function
input
terminal P4
define]
6 Multi-Step freq – Mid 3 O
7 Multi-Step freq – High
I21 A415 [Multi-
function
input
terminal P5
define]
8 Multi Accel/Decel – Low 4 O 7-14
9 Multi Accel/Decel – Mid
I22 A416 [Multi-
function
input
terminal P6
define]
10 Multi Accel/Decel – High 5 O
11 DC brake during stop 8-2
I23 A417 [Multi-
function
input
terminal P7
define]
12 2nd motor select 6 O 8-21
13 -Reserved- -
I24 A418 [Multi-
function
input
terminal P8
define]
14 -Reserved- 7 O -
15 Up-
down
Frequency increase
(UP)
command
8-4
16 Frequency decrease
command (DOWN)
17 3-wire operation 8-7
18 External trip: A Contact (EtA) 10-5
19 External trip: B Contact (EtB)
20 Self-diagnostic function 8-22
21
Change from PID operation to
V/F operation
8-10
22
2
nd
Source
8-24
23 Analog Hold 7-6
24 Accel/Decel Disable 7-16
25 Up/Down Save Freq. Initialization 8-4
26 JOG-FX 8-3
27 JOG-RX
* See “Chapter 14 Troubleshooting and maintenance” for External trip A/B contact.
* Each multi-function input terminal must be set differently.