Chapter 15 PID Function (Built-in function)
15 - 45
scope of water level sensor.
Output data type: 0 ~ 4000
- It converts the input 0 ~ 10V to digital value from 0 ~ 4000 and delivers it to basic unit.
- In the case, the resolving power of digital value 1 is 10/4000 = 2.5mV
Filter process, averaging: disabled
- The example sets the input values in order that filter process and averaging are not
available.
- For more information about each function, refer to 12 Analog I/O Module.
(3) D/A Output Module Parameter setting
(a) Set the parameter of D/A output module(XBF-DV04A) that output MV to a drive.
How to set them is as same as A/D input module. In the example, it is set as follows.
RUN CH: CH0 RUN
- In the example, MV is output as CH0 of D/A output module.
Output scope : 0 ~ 10V
Input data type: 0 ~ 4000