Chapter 8. Communication Driver 
8-29 
 
 
8.14 NAIS FP series : Mewtocol 
 
 
8.14.1 Communication Mode 
 
  Connection is available through FP series of PLC and Mewtocol of NAIS. 
  If connected with FP series, its applicable communication setting is as follows. 
  At this moment, the applicable communication setting of FP series and the XGT Panel to be connected between should be set 
identical to each other. 
 
Setting Contents 
Setting Item 
Tool Port  CH1/CH 2 
Remarks
Communication 
Mode 
RS-232C RS-232C,RS-422, RS-485  - 
Instrument Sided 
Connector 
Mini Din 5-Pin connector
5-Pin connector  - 
Connection 
Protocol 
Mewtocol - 
Communication 
Speed 
9,600bps(fixed) 2,400/9,600/19,200/38,400/57,600/115,200bps  - 
Data Bit  8Bits  7Bits, 8Bits  - 
Parity Bit  Odd (fixed) 
None, Odd, Even 
- 
Stop Bits 
1 Bit  1 Bit, 2Bits 
Station No. 
1 ~ 31  1 ~ 31 
- 
 
8.14.2 Connection Available Device 
 
  The range of the Read/Write available device with the XGT Panel connected is as shown below. 
  Max. range of the connection available device is diverse based on the connected type of PLC. 
 Max. available range is displayed in here. For more information on the Max. device range of each PLC, refer to the user’s 
manual of the applicable PLC. 
 
Connection Available Area 
Device 
Bit  Word  Long 
Remarks 
X Area 
X0 –X73F WX0 – WX73  DWX0 – DWX72 
Y Area 
Y0 –Y73F WY0 – WY73 
DWY0 – DWY72 
R Area 
R0 –R97F 
WR0 –WR97  DWR0 –DWR96 
L Area 
L0 –L63F WL0 – WL63  DWL0 – DWL62 
T Area 
T0 – T1023 
C Area 
C0 – C1023 
EV0 – EV1023  DEV0 –DEV1022 
D Area  - 
DT0 –DT32764 DDT0 –DDT32763 
R(Special) 
R9000 –R910F 
- - 
LD Area  - 
LD0 –LD127  DLD0 –DLD126 
D(Special)  -  DT90000 - 90259  DDT90000 - 90258 
-