Chapter 8. Communication Driver 
8-35 
 
 
8.17 LS XGK series Loader Protocol 
 
8.17.1 Communication Mode 
 
Connection is available through XGK series of PLC and the Loader Protocol. 
  Since Communication Speed and Communication Set are fixed, LS XGK series of Loader if selected makes the Communication 
Setting button inactive, thus setting is unavailable. 
 
Setting Item  Setting Contents  Remarks 
Communication Mode  RS-232C  CH2 Unavailable 
Instrument Sided Connector  9pin Male connector  - 
Connection Protocol  XGK Loader Protocol  - 
Communication Speed  115,200bps 
Data Bit  8Bits 
Parity Bit  None 
Stop Bits  1 Bit 
Station No.  None 
Fixed (Setting unavailable) 
 
8.17.2 Connection Available Device 
 
Device range of LS XGK series of PLC where Read or Write is available with the XGT Panel connected to is as follows. 
Max. range of the connection available device is diverse based on the connected type of PLC. 
Max. available range is displayed in here. For more information on the Max. device range of each PLC, refer to the user’s manual 
of the applicable PLC. 
 
Connection Available Area 
Device 
Bit  Word  Long 
Remarks 
P Area  P00000 - P2047F  P0000 - P2047  P0000 - P2046 
EX) PD0000F :   
P0’s bit 15 
M Area  M00000 - M2047F  M0000 - M2047  M0000 - M2046  - 
K Area 
K00000 - K2047F  K0000 - K2047  K0000 - K2046  - 
F Area  F00000 - F2047F  F0000 - F2047  F0000 - F2046  Read dedicated 
T Area  T0000 - T2047  T0000 - T2047  T0000 - T2046  - 
C Area  C0000 - C2047  C0000 - C2047  C0000 - C2046  - 
U Area  U00.00.0 - U7F.31.F  U00.00 - U7F.31 
U00.00 - U7F.30 
- 
S Area  S00.00 - S127.99  - 
- 
Bits Read 
unavailable 
L Area  L000000 - L11263F  L00000 - L11263 
L00000 - L11262 
- 
N Area  -  N00000 - N21503 
N00000 - N21502 
- 
D Area  D00000.0 - D32767.F  D00000 - D32767 
D00000 - D32766 
- 
ZR Area  -  ZR00000 - ZR65535 
ZR00000 - ZR65534 
-