Lucent Technologies Galaxy Power System 4812
13 - 12 Troubleshooting Millennium Systems Issue 5 June 2000
RECT Alarm LED
Table 13-E: Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT MAJ ID Not Configured None None Rectifier ID
number has
not been set.
1. Press ON/STBY
switch up and hold
for five seconds
until display starts
blinking “0”.
2. Release switch;
display should
continue to blink.
3. Depress switch and
release. Display
will increment up
one number on
each release of the
switch, but will
remain flashing.
4. Once the desired
ID number appears,
depress and hold
the switch for five
seconds. The
display will cease
to blink, and then
revert to the
rectifier current.
RECT MAJ ID Conflict None None Two or more
rectifiers have
the same ID
number.
See above.
RECT MAJ Multiple Rectifier
Fail
ALM None More than one
rectifier has an
ALM LED lit.
See alarms listed
below.
RECT MAJ High Voltage Alarm ALM HO •Lightning has
struck
system.
•Internal
rectifier
failure
1. Toggle the ON/
STBY switch into
the STBY position
and then back into
the ON position.
2. If the problem is
not corrected,
replace the rectifier.