Lucent Technologies Galaxy Power System 4812
Issue 5 June 2000 Troubleshooting Vector Systems 14 - 7
RECT Alarm LED
Table 14-E: Rectifier Related Alarms
Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Vector
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT MAJ rid None None Rectifier ID
number has not
been set.
1. Press ON/STBY
switch up and
hold for five
seconds until
display starts
blinking “0”.
2. Release switch;
display should
continue to blink.
3. Depress switch
and release.
Display will
increment up one
number on each
release of the
switch, but will
remain flashing.
4. Once the desired
ID number
appears, depress
and hold the
switch for five
seconds. The
display will cease
to blink, and then
revert to the
rectifier current.
RECT MAJ rid None None Two or more
rectifiers have
the same ID
number.
See above.
RECT MAJ nrFA ALM None More than one
rectifier has an
ALM LED lit.
See rectifier alarms
listed below.