14 - 12 Troubleshooting Vector Systems Issue 5 June 2000
BD Alarm LED or
No LED
Table 14-F: Miscellaneous Alarms
Controller
LED
Controller
Alarm
Status
Vector
Controller Display
Other
Indication(s)
Possible
Problem(s)
Possible Solution(s)
BD MAJ bod Rectifiers
may say
ACF.
Temporary
condition that
may be
associated with
other alarms
Call your local RTAC
representative.
None MAJ AUJ Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary
equipment
Call your local RTAC
representative.
None None None Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.
If a green LED
is lit despite a
contactor open
command
issued by the
controller, the
drive card or the
contactor has
failed.
Call your local RTAC
representative.
None None None -- Fuse has
operated.
Replace the controller fuse
labeled F1 (power).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Galaxy Power System 4812 and is the answer not in the manual?

Lucent Technologies Galaxy Power System 4812 Specifications

General IconGeneral
BrandLucent Technologies
ModelGalaxy Power System 4812
CategoryPower Supply
LanguageEnglish

Related product manuals