Lucent Technologies Galaxy Power System 4812
Issue 5  June 2000  Circuit Boards  8 - 3
Illustrations
BLJ and BIC 
Locations
Figure 8-1 shows the location of the BLJ Terminal Board and Bay 
Interface Card (BIC). 
Replacing a BIC Figure 8-2 shows the straps required prior to replacing a Bay Interface 
Card (BIC). (See “BIC Failure” in Table 13-C.) Straps are backups to 
ensure continous operation of LVBD and LVLD contactors. 
Figure 8-1: Location of BLJ Terminal Board and 
Bay Interface Card
BLJ BIC
Figure 8-2: Required Straps Prior to Replacing 
a Bay Interface Card (BIC)
BLJ2/3
Straps For Replacing BIC Board