14 - 10 Troubleshooting Vector Systems Issue 5 June 2000
RECT MIN rFA ALM LO Low output
voltage:
•Excessive
output current
•Internal
rectifier failure
1. Toggle the ON/
STBY switch
into the STBY
position and then
back into the ON
position.
2. If the problem is
not corrected,
replace the
rectifier.
RECT MIN rFA ALM ICS
IP5
IP6
IP7
Internal rectifier
failure
1. Place the ac
circuit breaker
for the rectifier in
the OFF position.
2. Remove the
rectifier from the
shelf.
3. Wait for 30
seconds or until
all front panel
display LEDs
have
extinguished.
4. Replace the
rectifier.
5. Return the ac
breaker to the ON
position.
6. Place the rectifier
ON/STBY switch
into the ON
position.
7. If the problem is
not corrected,
replace the
rectifier.
Table 14-E: Rectifier Related Alarms
Rectifier Related Alarms
(See Figures 12-6 and 12-8)
Controller
LED
Controller
Alarm
Status
Vector
Controller Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Galaxy Power System 4812 and is the answer not in the manual?

Lucent Technologies Galaxy Power System 4812 Specifications

General IconGeneral
BrandLucent Technologies
ModelGalaxy Power System 4812
CategoryPower Supply
LanguageEnglish

Related product manuals