12 - 6  Troubleshooting Preparations   Issue 5  June 2000
Reference Figures, continued
Millennium 
Controller
Basic Controller
BSH (microprocessor board): After power up, or after a reset, the 
green and yellow LEDs will both be lit while self diagnostics are in 
progress (which will take about 10 seconds). If all diagnostics pass, the 
yellow LED will extinguish and the green LED will remain lit. If a 
failure is detected during diagnostics, the green LED will extinguish and 
the yellow LED will remain lit. 
If a failure occurs during normal operation, the green LED will 
extinguish and the yellow LED will light. 
Intelligent Controller
BSJ (microprocessor board): After power up, or after a reset, the green 
and yellow LEDs will both be lit while self diagnostics are in progress 
(which will take about 30 seconds). If all diagnostics pass, the yellow 
LED will extinguish and the green LED will remain lit. If a failure is 
detected during diagnostics, the green LED will extinguish and the 
yellow LED will remain lit. If a terminal is attached to the local port 
during diagnostics, the diagnostic messages will show which test failed. 
If a failure occurs during normal operation, the green LED will 
extinguish and the yellow LED will light.