363-208-011, Appendix 1
NJ00675A-2 Dual Power Feed Unit Installation Procedure
Issue 1 November 1998 1-5
normal, it would be necessary to change out the DPFU in service (hot
swap) based on the possibility that the unit would not respond correctly to a
future primary failure.
Circuit breakers CBA and CBB are rated at 30 Amps. and protect the 10
gauge secondary wiring between the DPFU and the Power Interface Unit
(PIU) on the SLC-2000 equipment.
Fuses A and B (-48VDC & RTN), accessible at front panel, are associated
with the internally located monitoring circuit.
Fuses A and B are GMT type fuses and are rated at 1/2 Amp., 60 Volts.
The green Power LED will light when one or more input feeders is provid-
ing -48VDC.
Red Alarms LED (A) is associated with input A and will light if input A is not
present. When LED (A) is lit, a loop closure can be sent to associated SLC-
2000 System or elsewhere via terminals 1 and 2 of the Alarms terminal
block, located on the DPFU faceplate.
Red Alarms LED (B) is associated with input B and will light if input B is not
present. When LED (B) is lit, a loop closure can be sent to associated SLC-
2000 System or elsewhere via terminals 3 and 4 of the Alarms terminal
block, located on the DPFU faceplate.
If alarm signals are sent to the SLC-2000 use J171 connector, used for
miscellaneous discrete environmental alarms. See Section 3 for details.
Normal operation of the unit is as follows:
Green Power LED lit
Both red Alarms LED’s A and B extinguished
Both alarm outputs A and B are open
Both power outputs are active
In order for the DPFU to provide power on both outputs from a single input,
the circuit breakers or fuses feeding the inputs must be sized at 45 or50
Amps and the input wiring must be 6 gauge. In addition, the output wiring
from the DPFU to the
SLC
-2000 System must be 10 gauge.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies SLC-2000 Access System Central Office Terminal and is the answer not in the manual?

Lucent Technologies SLC-2000 Access System Central Office Terminal Specifications

General IconGeneral
BrandLucent Technologies
ModelSLC-2000 Access System Central Office Terminal
CategoryTouch terminals
LanguageEnglish

Related product manuals