10
FUSES / DISJONCTEURS / SICHERUNGEN -HRC Type(EN60269) - MCBs (EN60898)
FUSE RATING / TAILLE DES DISJONCTEURS / EMPFOHLENE SICHERUNG (A)
1Ph - 230 V (R407C, R22)
CC875
80 (L) (E) 110 (L) (E)
MCU+ S H1 H2 H3 H4 S H1 H2 H3 H4
60 20202020------
80 25 25 25 25 - 25 25 25 25 -
90 -----32323232-
MHPUL(E)
80 25 32 32 40 - 25 32 32 40 -
DCUE
60 25252525------
80 32 32 32 32 - 32 32 32 32 -
S = No Electric Heating / Sans Batterie Electrique / Ohne Elektroheizung
H = + Electric Heaters / + Batterie Electrique / Mit Elektroheizung
H1= 0.9 kW H2= 1.8 kW H3= 2.75 kW H4= 3.7 kW @ 230V
.
FUSE RATING / TAILLE DES DISJONCTEURS / EMPFOHLENE SICHERUNG (A/Ph)
3Ph - 400 V (R407C, R22)
CC875
80 (L) (E) 110 (L) (E) 140 (L) (E)
MCU+ S H1H2H3H4 S H1H2H3H4 S H1H2H3H4
60 10 10 16 16 16 - - - - - - - - - -
80 10 10 16 16 16 10 10 16 16 16 - - - - -
90 -----1616161616-----
100 -----16161616161616161616
130 ----------1616161616
150 ----------2525252525
MHPUL(E)
80 10 16 20 25 20 - - - - - - - - - -
100 -----1620202520-----
150 ----------2525323232
DCUE
60 16 16 16 16 16 - - - - - - - - - -
80 16 16 16 16 16 16 16 16 16 16 - - - - -
S = No Electric Heating / Sans Batterie Electrique / Ohne Elektroheizung
H = + Electric Heaters / + Batterie Electrique / Mit Elektroheizung
H1= 0.9 kW H2= 1.8 kW H3= 2.75 kW H4= 3.7 kW @ 230V
.
FUSE RATING / TAILLE DES DISJONCTEURS / EMPFOHLENE SICHERUNG (A)
CC875 E + MHPUE ONLY
(with separate supplies to electronic indoor and outdoor units)
Provided that both indoor and outdoor units are electronic (āEā) and control cables between them are data cables, the
units may be independently supplied and fused.
CC875 S H1 H2 H3 H4 UNIT SIZE 60 80 100 150
80E 5 10 16 16 16 DCUE 1Ph 25 32 - -
110E 5 10 16 16 16 MHPUE 1Ph - 20 - -
140E 5 10 16 16 16 DCUE 3Ph 16 16 - -
MHPUE 3Ph - 10 16 20
S = No Electric Heating / Sans Batterie Electrique / Ohne Elektroheizung
H = + Electric Heaters / + Batterie Electrique / Mit Elektroheizung
H1= 0.9 kW H2= 1.8 kW H3= 2.75 kW H4= 3.7 kW @ 230V
.