D33451 | Date 01/2018 21
Putting into operation
NOTICE
Important: make sure not to spill any water and make sure that no water flows past the water
tray and onto the floor, as this would cause the humidity to exceed the maximum values.
Fig. 10 Attach the sealing lip
Fig. 11 Push the water tray to the rear
panel
4.2.3 For appliances with active humidity control: Fill up and connect the water
tank
Fill the supplied water tank with water and use the enclosed tube to connect it to the “H
2
O”
connection on the rear of the chamber (Fig. 12).
4.3 CO
2
and N
2
connection
WARNING
Danger of explosion and poisoning when introducing gases/sub-
stances other than CO
2
and N
2
. Only carbon dioxide (CO
2
) and ni-
trogen (N
2
) may be introduced into the appliance through the gas
connections on the rear of the appliance.
WARNING
Gas bottles may burst or explode at high temperatures. Keep the gas
bottles away from open fl ames. Do not store gas bottles at or above
50 °C and ensure that the location is always well-ventilated. Prevent
water from penetrating as well as backfl ow into the gas bottles. It is
essential that you read the safety notes and instructions of the gas
supplier.
CAUTION
Danger of suffocation. CO
2
and N
2
can have a suffocating effect
in high concentrations. In normal mode, the appliance emits small
amounts of CO
2
and N
2
to its surroundings. You should therefore
ensure that the room in which it is installed is properly ventilated.
A ventilation rate of 250 m³ / h is required. Always close the stop
valve or pressure reducer on the gas bottles if the appliance is not in
operation.