1 7. APPENDICES
17.1 SPECIFICATIONS
■ GENERAL SPECIFICATIONS
Construction Panel ush mounting
Degree of protection IP66; Applicable to the front of the panel meter mounted according to the specied
panel cutout.
Connection M3 separable screw terminal (torque 0.6 N·m)
Screw terminal Nickel-plated steel (standard) or stainless steel
Housing material Flame-resistant resin (gray)
Isolation Input to DC output to HH output or H output to L output or LL output to power
Input waveform Up to 15% of 3rd harmonic content
Setting (front button) Scaling setting mode Input type, input scaling value A and B, display scaling value A and B, decimal
point position, analog output function mode, analog output 0% adjustment, analog
output 100% adjustment
Alarm setting mode Alarm point, HH, H, L and LL alarm setpoint, HH, H, L and LL trip action, HH, H,
L and LL deadband (hysteresis), HH, H, L and LL ON delay time, HH, H, L and LL
coil at alarm, main display blinking at alarm
Advanced setting mode Brightness, automatic return time to Measuring Mode, transition time to Lockout
Setting Mode, display refreshing rate, version indication
Lockout setting mode Alarm setting lockout, scaling setting lockout, advanced setting lockout, loop test
output lockout, initialization
Loop test output ----
Lockout setting Prohibiting certain operations; protecting settings
■ DISPLAY
Display 16 mm (.63) high, 4 ½ digits, 7-segment LED
Display range -19999 to 19999
Decimal point position 10
-1
, 10
-2
, 10
-3
, 10
-4
, or none
Zero indication Higher-digit zeros are suppressed
Over-range indication ‘-19999’ or ‘19999’ blinking for display values out of the display range
‘S.ERR’ and ‘Min’ or ‘Max’ blinking when the input signal is out of the usable range
Alarm status indication LL indicator Green turns on when the LL alarm is tripped
L indicator Green turns on when the L alarm is tripped
H indicator Red turns on when the H alarm is tripped
HH indicator Red turns on when the HH alarm is tripped
P indicator Amber turns on when none of the other alarms is tripped
Only ‘P’ turns on with no-alarm-output type. ‘LL’ or ‘HH’ does not turn on with dual-
alarm-output type.
All setpoints can be independently set either for Hi or Lo alarm trip.
Function indicators Zro, Spn, D/P, Tch, Fnc, Min, Max
Display mode status and operation status, amber ON or blink