17.3 PARAMETER LIST
MODE PARAMETER SETTING RANGE INDICATOR DISPLAY DEFAULT
VALUE
DECIMAL
POINT
POSITION
UNIT
Measuring Present value -19999 – 19999
, , ,
,
---- ----
*1
User-dened
MAX value -19999 – 19999
---- ----
*1
User-dened
MIN value -19999 – 19999
---- ----
*1
User-dened
LL alarm setpoint -19999 – 19999
---- ----
*1
User-dened
L alarm setpoint -19999 – 19999
---- ----
*1
User-dened
H alarm setpoint -19999 – 19999
---- ----
*1
User-dened
HH alarm setpoint -19999 – 19999
---- ----
*1
User-dened
Scaling
setting
Input type 45 – 55 Hz, 55 – 65 Hz,
45 – 65 Hz, 350 – 450 Hz,
10 – 500 Hz
,
, , ,
,
---- ----
Input scaling value A H50 40.00 – 60.00
,
to
---- Hz
H60 50.00 – 70.00
to
H55 40.00 – 70.00
to
H400 300.0 – 500.0
to
HF 5.0 – 600.0
to
Display scaling value A -19999 – 19999
,
to
*1
User-dened
Input scaling value B H50 40.00 – 60.00
,
to
---- Hz
H60 50.00 – 70.00
to
H55 40.00 – 70.00
to
H400 300.0 – 500.0
to
HF 5.0 – 600.0
to
Display scaling value B -19999 – 19999
,
to
*1
User-dened
Decimal point position No decimal point,
or 10
-1
to 10
-4
, ,
, ,
---- ----
Analog output function
mode
Proportional to the display
value,
Proportional to the scaling
value
,
---- ----
Analog output 0%
adjustment
Adjustable range
-5 to +105%
,
:
(increasing)
(decreasing)
0% output ---- ----
Analog output 100%
adjustment
Adjustable range
-5 to +105%
,
:
(increasing)
(decreasing)
100%
output
---- ----
Alarm
setting
Alarm point 1: Quad alarm
, , ,
,
( , , )
,
---- ----
2: Dual alarm
, ,
LL alarm setpoint -19999 – 19999
,
to
*1
User-dened
LL trip action High trip, low trip
,
,
---- ----
LL deadband
(hysteresis)
0000 – 9999
, ,
to
---- User-dened
LL ON delay time 00 – 99
, ,
to
---- Second
LL coil at alarm Coil energized at alarm,
de-energized at alarm
,
,
---- ----
*1 Conforms to decimal point position setting.
NOTE 1: Indicators with the present value in Measuring Mode depend on the set alarm trip action.
NOTE 2: INDICATOR: = ON, = Blinking
NOTE 3: 1 and 2 in the column of Alarm point in Alarm Setting Mode show alarm output codes.
NOTE 4: The indicators in parentheses in the column of Alarm point in Alarm Setting Mode show those with dual alarm selected.