8.5 ON DELAY TIME
Alarm output is provided when the display value exceeds the setpoint and stayed for the specied time duration, which pre-
vents the alarm output from being provided by a sudden change such like external disturbance. This time duration is called
ON delay time and can be set within the range of 0 to 99 seconds. The default value is 0 second.
8.5.1 OPERATING PROCEDURE
NOTE
• The following gures are display examples. The dis-
plays depend on the settings.
• With “Dual alarm” selected for the alarm point param-
eter, the LL and HH ON delay times are disabled.
1
Hold down Alarm/↓ button for 3 seconds or more to move on
to Alarm Setting Mode.
• The alarm point is indicated.
• ‘HH’, ‘H’, ‘L’, ‘LL’ and ‘Fnc’ indicators turn on.
NOTE
• ‘ALM2’ or ‘ALM4’ is indicated depending on the setting.
• When “Dual alarm” is selected for the alarm point parameter, ‘HH’ and ‘LL’ indicators do not turn on.
2
Press Alarm/↓ or Scale/↑ button to go to the LL (L, H or HH) ON
delay time setting.
• The LL (L, H or HH) ON delay time is indicated.
• ‘LL’ (‘L’, ‘H’ or ‘HH’) indicator blinks, ‘D/P’ and ‘Fnc’ indicators turn
on.
NOTE
The ON delay time is indicated within the range of 00 to 99 depending on the setting.
1,2,
5
2,5
3,4
4
Blinking
Blinking
■L ON delay
time
■H ON delay
time
■HH ON dela
time