2047LHZ EM-9517-B Rev.10
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
NOTE
Example of contact protection circuit with inductive load
Power
47LHZ
Inductive load
Varistor RC
circuit
Diode
C
R
Power
47LHZ
Inductive load
Varistor RC
circuit
C
R
U
U
* It is effective to connect a varistor across a load with the supply voltage 24 to 28 V, and across a contact with 100 to 200 V.
1.6.7 WIRING POWER
Connect power according to the power input code. The power specications are shown in the
following table.
CODE RATING PERMISSIBLE RANGE
M2 100 to 240 V AC 85 to 264 V AC, 50/60 Hz approx. 6.5 VA
R 24 V DC ±10% approx. 3 W
P 110 V DC 85 to 150 V DC approx. 3 W
IMPORTANT
• For safety, make sure that wiring is performed by qualied personnel only.
• In order to prevent potential electric shock, wire the unit after turning off the power supply and making sure that the
power is not supplied to the cable.
• Use wires as thick as possible and twist them from the end.
• For DC power, conrm the polarity.
Power
+
10
9
U(+) V(–)