2.1.3 BASIC SETTING PROCEDURE
The following shows the procedure to set the input to 25 – 65 Hz and the display to 25.00 – 65.00 Hz as an example. Set
values meeting signals of an equipment to use. Refer to 3. SETTING INPUT TYPE for details of setting.
PARAMETER LIST FOR BASIC SETTING
Parameters used in the basic setting are as shown in the following table.
PARAMETER SETTING VALUE FUNCTION INDICATOR SETTING
Input type HF Zro, Spn Measuring range: 10 – 500 Hz
Input scaling value A 025.0 Zro, Tch 0% input: 25.0 Hz
Display scaling value A
2500
*1
Zro, D/P 0% display: 25.00 Hz
Input scaling value B 065.0 Spn, Tch 100% input: 65.0 Hz
Display scaling value B
6500
*1
Spn, D/P 100% display: 65.00 Hz
Decimal point position 65.00 D/P 2 decimal places (10
-2
)
*1 The decimal point position depends on the decimal point position setting.
BASIC SETTING PROCEDURE
The basic setting procedure is as follows.
1
Conrm the wiring, turn on the power and move on to Scaling Setting Mode (measurement stopped).
• Hold down Scale/ button for 3 seconds or more.
2
Set input type.
• Press Shift button to shift the display into the setting standby mode and Up button to select the input type.
3
Set scaling values in the order of input scaling value A, display scaling value A, input scaling value B and
display scaling value B.
Press Alarm/ or Scale/ button to apply the new setting and go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode.
• Press Shift button to go to the next digit and Up button to change the blinking value.
4
Set decimal point position.
Press Alarm/ or Scale/ button to apply the new setting and go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode and Up button to select the decimal point posi-
tion.
5
Return to Measuring Mode (measurement started).
Hold down Alarm/ or Scale/ button for 1 second or more to apply the new setting and return to Measuring Mode.