8647LHZ EM-9517-B Rev.10
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
12.2 OPERATING PROCEDURE
NOTE
The following gures are display examples. The displays
depend on the settings.
1
Hold down Alarm/↓, Scale/↑ and Shift buttons at once for 5
seconds or more to move on to Loop Test Output Mode.
• The measuring is stopped and the last measured values or status
are held for the DC and alarm outputs.
• The current indication starts blinking, to which you can apply
changes.
• ‘Zro’, ‘Spn’, ‘D/P’, ‘Tch’, ‘Fnc’ and ‘Max’ indicators turn on.
NOTE
• In moving on to Loop Test Output Mode while ‘S.ERR’ is indicated, -10% of the display scaling span or ‘-19999’ is
indicated when ‘Min’ indicator blinks, and 110% of the display scaling span or ‘19999’ is indicated when ‘Max’ indicator
blinks.
• In moving on to Loop Test Output Mode while ‘-19999’ blinks, -10% of the display scaling span or ‘-19999’ is indicated.
• In moving on to Loop Test Output Mode while ‘19999’ blinks, 110% of the display scaling span or ‘19999’ is indicated.
• The specied decimal point position is applied.
1,3
1,3
1,2
2
Blinking