2947LHZ EM-9517-B Rev.10
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
3.1 INPUT TYPE LIST
DISPLAY FUNCTION OPERATIONAL RANGE DEFAULT VALUE
H55 Measuring range 45 – 65 Hz 40 – 70 Hz H55
H400 Measuring range 350 – 450 Hz 300 – 500 Hz
HF Measuring range 10 – 500 Hz 5 – 600 Hz
H50 Measuring range 45 – 55 Hz 40 – 60 Hz
H60 Measuring range 55 – 65 Hz 50 – 70 Hz
3.2 OPERATING PROCEDURE
Procedures to change ‘H55’ (measuring range 45 – 65 Hz) (default) to ‘HF’ (measuring range 10 – 500 Hz) are described
here.
NOTE
The left gure shows a display example (default input
type). The display depends on the settings. The display
depends on the settings. Refer to 3.1 INPUT TYPE
LIST for details.
1
Conrm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then
the display moves on to Measuring Mode.
NOTE
Indication ‘S.ERR’ may blink, which shows the input out of the measur-
ing range and does not show the unit failure.
2
Hold down Scale/↑ button for 3 seconds or more to move on to
Scaling Setting Mode.
• The input type is indicated.
• ‘Zro’ and ‘Spn’ indicators turn on.
NOTE
Some alarm indicators turn on with the function indicators. The alarm indication is due to the last status before mode
transition held but does not show the unit failure.
5
2,5
3
4
■ Immediately after power on (all indicators on)
■ Measuring Mode
*1 Display depends on the settings and input.