1747LHZ EM-9517-B Rev.10
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
1.6 WIRING INSTRUCTIONS
1.6.1 CAUTION IN WIRING
• For safety, make sure that wiring is performed by qualied personnel only.
• In order to prevent potential electric shock, wire the unit after turning off the power supply and making sure that the power
is not supplied to the cable.
• Be sure to conrm the name and polarity of each terminal before wiring to it.
• Do not connect anything to unused terminals.
• We offer a series of lightning surge protectors for protection against induced lightning surges. Please contact us to
choose appropriate models.
1.6.2 RECOMMENDED SOLDERLESS TERMINAL
• Use solderless terminals for M3. Refer to the drawings below.
Applicable wire size: 0.25 to 1.65 mm
2
Torque: 0.6 N·m
Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
IMPORTANT
• Insulated solderless terminals are recommended.
• In using non-insulated solderless terminals, cover them with insulating caps or tubes.
• Ring tongue terminals are recommended rather than spade tongue terminals to prevent from falling off.
1.6.3 TERMINAL ASSIGNMENT
6 (.24) max
6 (.24) max 3.3 (.13) max
3.3 (.13) max
unit: mm (inch)
Input signal PowerDC output
Alarm output
Input signal
DC output Power
NO ALARM OUTPUT ALARM OUTPUT