10547LHZ EM-9517-B Rev.10
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■ PERFORMANCE
Accuracy Display ±0.1 Hz; ±1 Hz at 70 Hz or more (input 50 – 300 V)
Output ±0.1% (DC output = display + output)
Temp. coefficient ±0.015%/°C (±0.008%/°F)
Input resolution Max. 0.01 Hz
Output resolution Max. 14 bits
Response time ≤ 0.5 second except for 45 Hz or less (alarm output: 0 – 100% at 90% setpoint)
≤ 0.5 second except for 45 Hz or less (DC output: 0 – 90%)
Line voltage effect ±0.1% over voltage range
Insulation resistance ≥ 100 MΩ with 500 V DC
Dielectric strength 2000 V AC @ 1 minute (input to DC output to HH output or H output to L output or
LL output to power to ground)
■ STANDARDS & APPROVALS
EU conformity EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category III (input)
Measurement Category II (alarm output)
Installation Category II (power)
Pollution Degree 2
Input or DC output to alarm output to power: Reinforced insulation (300 V)
Input to DC output: Basic insulation (300 V)
RoHS Directive
Protection against access to the terminal blocks Finger protection (VDE 0660-514)