EasyManua.ls Logo

Mhouse SL1 - Page 16

Mhouse SL1
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Instructions SL1
5 Refer to figure 54 for the electrical extra low voltage connection of the
various devices to the control unit terminals.
The terminals have the same colour coding as the corresponding
devices; for example, the grey terminal (OPEN) of the KS1 selector must
be connected to the grey terminal (OPEN) of the control unit.
For most connections you do not need to observe any polarity; only
for the shielded cable of the aerial it is necessary to connect the central
core and the shield as shown in detail [A].
The terminals can be removed in order to facilitate the operations [A] as
shown in figure 55; make the connections and then reinsert them.
When you have completed the connections, use clamps to secure the
cables to the appropriate fasteners [B].
6Close the side cover of the SL1K gear motor by sliding it on from
above and tighten the screw with a screwdriver.
FL1
PH1
PH1
KS1
SL1K
Figure 54
B
A
Figure 55
Figure 56
B
TX
RX

Table of Contents

Related product manuals