Indicators, Controls and Operations
The individual zone LED (if programmed) turns OFF.
The alarm event is cancelled. No log reference.
The fire alarm system returns to normal.
If at any time during the Positive Alarm Sequence a second alarm (PAS or otherwise) is
actuated, the fire alarm will go into evacuation mode. In a preconfigured FACP the Positive
Alarm Sequence may be enabled or disabled as the user requires.
11.6 Enabling or Disabling the Positive Alarm Sequence
To enable or disable the Positive Alarm Sequence, from the Keypad of the FACP press
“M” to enter the Menu
Using the Up and Down Arrow buttons, scroll to “Operation” and press the enter key
In the Operation Menu scroll to “Positive Alarm” and press enter
You will now see displayed the current status of the Positive Alarm Sequence and will be
prompted to change status.
If you wish to change the status press the “enter” key.
If you do not wish to change the status, press the “cancel” key
11.7 Input Types
Table 5 shows input types available for programming.
Note: There will be no notification message advising a change of status
Table 5 Input Types
Input Types Description
Non-Verified
Alarm
When an un-bypassed non-verified alarm input goes into alarm the common alarm
sequence is activated. Un-bypassed relay, signal, and strobe outputs are updated
according to their programming and alarm zone status indicators associated with the
input are activated. Alarm input activations are displayed on the shared display in the
common queue with alarm as the highest priority and is displayed first.
A pre-alarm condition on a device configured as an alarm input is displayed on the
shared display and on the alarm zone status indicator. If the pre-alarm condition is
restored the status will be cleared. If the input goes from pre-alarm to alarm, the pre-
alarm status will be replaced with the alarm status for the input.
Once an alarm input is in alarm the alarm condition is latched until system reset
(changes in status from alarm to pre-alarm or to normal are ignored).
Pos Alarm disabled
Enable ? Y
i

Table of Contents

Other manuals for Mircom FX-350 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FX-350 Series and is the answer not in the manual?

Mircom FX-350 Series Specifications

General IconGeneral
BrandMircom
ModelFX-350 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals