5 MULTIPLEXER REPLACEMENT
5 - 3
Item A60MX
Overall accuracy ±0.3% (Digital output value ±12)
Absolute
maximum input
Voltage ±15V
Current ±30mA
Analog input points 16 channels/module
Multiplexer element IC relay
Isolation method
Between the input terminal and programmable controller: photocoupler isolation
Between channels: non-isolated (1M resistor isolation)
Occupied I/O points
16 points (treated as empty slots)
(0 point setting is possible by I/O assignment.)
Connected terminal 38-point terminal block
Applicable wire size
0.75 to 2mm
2
(Applicable tightening torque: 39 to 59N•cm)
Applicable solderless terminal V1.25-3, V1.25-YS3A, V2-S3, V2-YS3A
Internal current consumption
(5VDC)
0.65A
Weight 0.55kg