EasyManua.ls Logo

Mitsubishi Electric MELSEC-A/QnA Series - Page 217

Mitsubishi Electric MELSEC-A/QnA Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 MULTIPLEXER REPLACEMENT
5 - 4
*1 Analog output (voltage) to the A616AD, processing analog input values of the A60MX.
The I/O characteristics and the maximum resolution are to be the same as in the specifications of the A616AD as below.
: Compatible, : Partial change required, ×: Incompatible
Q68ADV Q68ADI Compatibility Precautions for replacement
A60MX is the accuracy in
respect to the full scale, and
Q68ADV/I is the accuracy in
respect to maximum digital
output value.
±15V -
- ±30mA
8 channels/module
Consider replacement with
multiple Q68ADV/I.
--
Between the I/O terminal and programmable controller power supply:
photocoupler isolation
Between channels: non-isolated
16 points
(I/O assignment: intelligent 16 points)
Q68ADV/I cannot set to 0 point
with I/O assignment.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
R1.25-3 (A solderless terminal with sleeve can not be used.) ×
0.64A 0.64A
0.19kg 0.19kg
Input Analog input range Maximum resolution Digital output value
Voltage (V)
0 to +10 2.5mV (1/4000)
0 to 4000
-2000 to 2000
0 to +5 1.25mV (1/4000)
+1 to +5 1.0mV (1/4000)
-10 to +10 5.0mV (1/4000)
-5 to +5 2.5mV (1/4000)
Current (mA)
0 to +20 10μA (1/2000)
0 to 2000
-2000 to 0
0 to +20 5μA (1/4000)
0 to 4000
-2000 to 2000+4 to +20 4μA (1/4000)
-20 to +20 20μA (1/2000)
1000 to 3000
-1000 to 1000
-20 to +20 10μA (1/4000)
0 to 4000
-2000 to 2000

Table of Contents

Related product manuals