5 MULTIPLEXER REPLACEMENT
5 - 10
: Compatible, : Partial change required, ×: Incompatible
Q64AD-GH Compatibility Precautions for replacement
-10 to 0 to +10VDC (Input resistance value: 1M)
0 to 20mADC (Input resistance value: 250) The minus current cannot be input.
--
Analog output voltage to the
A616AD
With A60MXR, equivalent or more
resolution value can be obtained
by setting at the analog inputs,
range of -10 up to 10V/high
resolution mode, and User range
while the analog inputs are used at
the range of -5 up to 5V on
Q64AD-GH.
When using a range of -20 up to
+20mA (with A60MXR), negative
current can not be converted with
Q64AD-GH.
Use conversion devices to convert
into a input range.
A60MXR is the accuracy in respect
to the full scale, and Q64AD-GH is
the accuracy in respect to
maximum digital output value.
±15V
±30mA
4 channels/module
Consider replacement with
multiple Q64AD-GH.
--
16 points
(I/O assignment: intelligent 16 points)
Q64AD-GH cannot set to 0 point
with I/O assignment.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
R1.25-3 (A solderless terminal with sleeve can not be used.) ×
0.89A
The recalculation of internal
current consumption [5VDC] is
required.
0.2kg
Input Analog input range
Maximum resolution Digital
output value
(32 bits)
Digital
output value
(16 bits)
32 bits 16 bits
Voltage
0 to 10V 156.3µV 312.6µV
0 to 64000 0 to 32000
0 to 5V 78.2µV 156.4µV
1 to 5V 62.5µV 125.0µV
User range settings
(Uni-polar)
47.4µV 94.8µV
-10 to 10V 156.3µV 312.6µV
-64000 to 64000 -32000 to 32000
User range settings
(Bi-polar)
47.4µV 94.8µV
Current
0 to 20mA 312.5nA 625.0nA
0 to 64000 0 to 32000
4 to 20mA 250.0nA 500.0nA
User range settings
(Uni-polar)
151.6nA 303.2nA
Reference accuracy
±0.05%
Digital output value (32 bit)
±32 digits
Digital output value (16 bit)
±16 digits
Temperature coefficient
±71.4ppm/°C (0.00714%/°C)
Specific isolated area
Isolation
method
Dielectric withstand
voltage
Insulation
resistance
Between the I/O terminal and
programmable controller power supply
Photocoupler
isolation
1780VrmsAC/3 cycles
(Altitude 2000m)
500VDC,
10M
or more
Between analog channels
Transformer
isolation