3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 22
: Compatible, : Partial change required, ×: Incompatible
Q62DAN Compatibility Precautions for replacement
Between the I/O terminal and programmable controller power supply:
photocoupler isolation
Between output channels: non-isolation
Between external power supply and analog output: transformer isolation
Between the I/O terminal and programmable controller power supply:
500VAC, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 20M or more
16 points
(I/O assignment: intelligent 16 points)
The number of occupied I/O points
has changed to 16 points.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
R1.25-3
(Sleeved solderless terminal cannot be used.)
×
0.33A
24VDC +20%, -15%
Ripple, spike 500mV
P-P
or less
0.15A
2.5A, 250µs or less
0.19kg