EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R-R6SFM - Page 170

Mitsubishi Electric MELSEC iQ-R-R6SFM
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
168
10 TEST FUNCTION
10.2 Device test with execution conditions
Addition/deletion/change of labels by the online change (ladder block)
When SM940 (Operation setting of the device test with execution conditions) is off, if local labels or program files are
added, deleted, or changed and the online change (ladder block) is performed, all the registrations that specify local labels
of the relevant program file are disabled. When SM940 is on, the registrations are not disabled.
*1
When SM940 is off, if global labels are added, deleted, or changed and the online change (ladder block) is performed, all
the registrations that specify global labels are disabled. When SM940 is on, the registrations are not disabled.
*1
*1 If reassignment of local labels/global labels which are used in the program is performed when SM940 is on, registrations including
reassigned labels are disabled. When SM940 is on, do not delete or change local labels or global labels registered to device tests with
execution conditions. If deleted or changed, registered settings may not be read correctly.
File batch online change
All the device tests with execution conditions registered to the target program for the file batch online change are disabled.
When global labels are added, deleted, or changed and the file batch online change is performed, all the registrations that
specify global labels are disabled.

Table of Contents

Related product manuals