1  RUNNING A PROGRAM
1.5  Program Execution Type
55
1
Fixed scan interval setting
Set the execution condition of the fixed scan execution type program.
[CPU Parameter]  [Program Setting]
"Program Setting" window
1. Click "Detailed Setting" on the 
"Program Setting" window.
"Detailed Setting" window
2. Select the program name and set 
the execution type to "Fixed Scan".
3. Click "Detailed Setting Information".
"Fixed Scan Execution Type Detailed Setting" window
4. Set the fixed scan interval.
Item Description Setting range Default
Specified Time 
Intervals
Sets the fixed scan interval to execute the fixed scan execution type 
program.
• When "ms" is selected: 0.5 to 60000ms (in 
increments of 0.5ms)
• When "s" is selected: 1 to 60s (in increments 
of 1s)
Unit Selects the unit for the fixed scan interval. • ms
•s
ms