APPX
Appendix 1 Error Codes
715
A
1A70H
to
1A73H
Safety
communications
receipt data
error
The received data is abnormal. Continue SIL2 Process CPU
Check the detailed information (safety
station system configuration
information) of the error by executing
module diagnostics using the
engineering tool and check "Station
No.", "Slot No. (another station)", and
"Base No. (another station)". If the
destination station is an intelligent
device station, execute the system
monitor for the remote head module in
the station and check the error details.
The possible cause is a hardware
failure of the module performing safety
communications. Please consult your
local Mitsubishi representative.
Safety CPU
Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
displayed station number. If the
destination station is a remote device
station or remote I/O station, read error
history data of the destination station
by executing a command from the CC
IE Field Configuration window, and
check the details of the error. If the
destination station is a master/local
station, execute the system monitor for
the station, and check the details of the
error.
The possible cause is a hardware
failure of the module performing safety
communications. Please consult your
local Mitsubishi representative.
System
configuration
information,
safety station
system
configuration
information
At interrupt
occurrence
1A80H Timeout in
safety
communications
Safety communications with a
destination station could not be
resumed within a safety I/O hold
time.
Continue Check and correct the safety I/O hold
time.
The possible cause is malfunction due
to noise or cable failure. Check that
there is no error in a transmission path
by executing CC-Link IE Field
diagnostics. Check the distance of
wires and cables and the grounding
status of each device as well.
Check the detailed information (safety
station system configuration
information) of the error by executing
module diagnostics using the
engineering tool and check "Station
No.", "Slot No. (another station)", and
"Base No. (another station)". If the
destination station is an intelligent
device station, execute the system
monitor for the remote head module in
the station and check the error details.
The possible cause is a hardware
failure of the module performing safety
communications. Please consult your
local Mitsubishi representative.
Safety station
system
configuration
information
At interrupt
occurrence
1B00H Network
configuration
mismatch
The CC-Link IE Field Network
configuration differs between the
systems A and B. (The error is
detected in the standby system.)
Continue Check that all network cables are
connected correctly.
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the network
cable. Please consult your local
Mitsubishi representative.
System
configuration
information
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing