720
APPX
Appendix 1 Error Codes
2022H Module
configuration
error
A power supply module other than
the redundant power supply
module has been mounted on the
redundant power supply base unit.
Stop Mount only the redundant power
supply module. If the same error code
is displayed again, the possible cause
is a hardware failure of the power
supply module, CPU module, or base
unit. Please consult your local
Mitsubishi representative.
System
configuration
information
At power-on,
at RESET
2040H CPU module
configuration
error
The number of CPU modules set
in the system parameters ("I/O
Assignment Setting") differs from
the number of CPU modules
actually mounted.
The CPU module is mounted on
the slot different from the one
specified in the system
parameters (I/O assignment
setting).
Two or more Safety CPUs are
mounted.
Stop Correctly set the number of CPU
modules (including the empty setting)
in the system parameters in
accordance with the number of CPU
modules actually mounted.
Correctly set the system parameters so
that the setting and actual CPU module
mounting status will be the same.
Mount only one Safety CPU.
System
configuration
information
At power-on,
at RESET
2041H CPU module
configuration
error
The CPU module is not mounted
on the slot that is set for the CPU
module in the system parameters
("I/O Assignment Setting").
The CPU module is mounted on
the slot that is set for empty in the
system parameters ("I/O
Assignment Setting").
An I/O module or intelligent
function module is mounted
between the CPU modules.
Arrangement of CPU modules
mounted is not appropriate to
configure a multiple CPU system.
Stop Check and correct the I/O assignment
setting in the system parameters.
Correctly set the number of CPU
modules (including the empty setting)
in the system parameters in
accordance with the number of CPU
modules actually mounted.
Remove the I/O module or intelligent
function module mounted between the
CPU modules.
System
configuration
information
At power-on,
at RESET
2043H CPU module
configuration
error
The CPU module is mounted on
the inapplicable slot.
Stop Mount the CPU module on the
applicable slot (CPU slot or I/O slot 0 to
6).
Remove the CPU module from the
inapplicable slot.
System
configuration
information
At power-on,
at RESET
2044H CPU module
configuration
error
The host CPU No. set in the
system parameters ("I/O
Assignment Setting") differs from
the one determined by the
mounting position of the CPU
module.
Stop Re-set the host CPU No. in the system
parameters in accordance with the
mounting position of the CPU module.
System
configuration
information
At power-on,
at RESET, at
STOP RUN
sta
te
2046H CPU module
configuration
error
Another CPU module was
accessed, but there was no
response.
Stop Check and correct the I/O assignment
setting in the system parameters.
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of another CPU
module. Please consult your local
Mitsubishi representative.
System
configuration
information
Always
2050H CPU module
configuration
error
An unsupported CPU module is
mounted.
Stop Remove the unsupported CPU
module. If all the CPU modules are
supported, the possible cause is a
hardware failure of the CPU module or
base unit. Please consult your local
Mitsubishi representative.
System
configuration
information
At power-on,
at RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing