APPX
Appendix 1 Error Codes
721
A
2051H CPU module
configuration
error
A CPU module that does not
support the online module change
(direct change) function is used in
a multiple CPU system.
Stop Refer to the MELSEC iQ-R Online
Module Change Manual, and correct
the system configuration.
To disable the online module change
(direct change) function, set "Direct
change setting" to "Disable" in the CPU
parameters. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or base unit. Please consult your local
Mitsubishi representative.
System
configuration
information
At power-on,
at RESET
2052H CPU module
configuration
error
A multiple CPU system was
configured with CPU modules
incompatible with multiple CPU
systems.
Stop Check and correct the system
configuration.
System
configuration
information
At power-on,
at RESET
2060H Base unit
configuration
error
Eight or more extension base
units are connected.
Stop Reduce the number of extension base
units to seven or less.
System
configuration
information
At power-on,
at RESET
2061H Base unit
configuration
error
Any of the following base units is
connected: QA1S3B,
QA1S5B/QA1S6B, QA6B,
QA6ADP+A5B/A6B, or
QA1S6ADP-S1+A1S5B/
A1S6B.
Stop Remove the inapplicable base unit:
QA1S3B, QA1S5B/QA1S6B,
QA6B, QA6ADP+A5B/A6B, and
QA1S6ADP-S1+A1S5B/A1S6B.
System
configuration
information
At power-on,
at RESET
2063H Base unit
configuration
error
Extension base unit levels are
overlapping.
Stop Check and correct the level setting of
the extension base units.
System
configuration
in
formation
At power-on,
at RESET
2070H Base unit
configuration
error
An unsupported base unit is
connected.
A GOT is bus-connected to the Q
series extension base unit.
Stop Disconnect the unsupported base unit.
If all the base units are supported, the
possible cause is a hardware failure of
the CPU module or base unit. Please
consult your local Mitsubishi
representative.
Disconnect the GOT bus-connected to
the Q series extension base unit.
System
configuration
information
At power-on,
at RESET
2080H Inter-module
synchronization
configuration
error
An inter-module synchronization
signal error has been detected.
Stop The possible cause is a hardware
failure of the CPU module, base unit, or
module (I/O module or intelligent
function module) connected. Please
consult your local Mitsubishi
representative.
System
configuration
information
At power-on,
at RESET
20E0H Module
unrecognized
CPU module
A module that the CPU module
cannot recognize is mounted.
In a multiple CPU system, the
module cannot be recognized
because the control CPU setting
in the system parameters is
different from that of other CPU
modules.
Redundant function module
Data communications with the
CPU module cannot be
performed.
Stop CPU module
Mount only applicable modules.
Correct the system parameter settings
for the CPU No.2 and later in
accordance with those of the CPU
No.1.
The possible cause is a hardware
failure of the I/O module or intelligent
function module accessed. Please
consult your local Mitsubishi
representative.
Redundant function module
The possible cause is a hardware
failure of the CPU module. Please
consult your local Mitsubishi
representative.
System
configuration
information
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents